347324287
|
0830600
|
2024-03-04
|
50 WILLIAM WHITE BLVD, PUEBLO, CO, 81001
|
|
Inspection Type |
Planned
|
Scope |
Partial
|
Safety/Health |
Safety
|
Close Conference |
2024-03-06
|
Emphasis |
N: CHEMNEP, P: CHEMNEP
|
Case Closed |
2024-11-04
|
Related Activity
Type |
Inspection |
Activity Nr |
1732438 |
Safety |
Yes |
|
Type |
Inspection |
Activity Nr |
1732435 |
Safety |
Yes |
|
Violation Items
Citation ID |
01001A |
Citaton Type |
Serious |
Standard Cited |
19100038 D |
Issuance Date |
2024-08-23 |
Abatement Due Date |
2024-09-30 |
Current Penalty |
0.0 |
Initial Penalty |
11524.0 |
Final Order |
2024-09-17 |
Nr Instances |
1 |
Nr Exposed |
260 |
Gravity |
5 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1910.38(d): The employer did not have and maintain an employee alarm system with a distinctive signal for each purpose so that it complied with the requirements of 1910.165: (a) On or about March 4, 2024, and at times prior, the employer did not maintain an alarm system with distinctive signal for each purpose which complied with 29 CFR 1910.165. There is one overhead alarm sound and employees rely on radio communication to determine whether the emergency requires shelter-in-place or evacuation. |
|
Citation ID |
01001B |
Citaton Type |
Other |
Standard Cited |
19100165 B01 |
Issuance Date |
2024-08-23 |
Abatement Due Date |
2024-09-30 |
Current Penalty |
11524.0 |
Initial Penalty |
0.0 |
Final Order |
2024-09-17 |
Nr Instances |
1 |
Nr Exposed |
20 |
Gravity |
5 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1910.165(b)(1): The employee alarm system did not provide warning for necessary emergency action as called for in the emergency action plan, or for reaction time for safe escape of employees from the workplace or the immediate work area, or both: (a) On or about March 4, 2024, and at times prior, Goodrich Corporation as the contract employer did not ensure that contract employees were provided warning for necessary emergency action as outlined in the emergency action plan. Contract employees do not carry radios, which is considered the primary method of communicating an emergency on the Goodrich Corporation facility. Contractors may work unsupervised in areas of the facility without means of emergency notification. Note: In small workplaces with 10 or less employees, direct voice communication (shouting) is an acceptable method for warning. |
|
|
345718738
|
0830600
|
2022-01-06
|
50 WILLIAM WHITE BLVD, PUEBLO, CO, 81001
|
|
Inspection Type |
Planned
|
Scope |
NoInspection
|
Safety/Health |
Health
|
Close Conference |
2022-01-06
|
Emphasis |
L: Aircraft, P: Aircraft
|
Case Closed |
2022-01-06
|
|
340882133
|
0830600
|
2015-08-24
|
50 WILLIAM WHITE BLVD, PUEBLO, CO, 81001
|
|
Inspection Type |
Planned
|
Scope |
Partial
|
Safety/Health |
Safety
|
Close Conference |
2015-08-27
|
Emphasis |
N: PSMPQV, P: PSMPQV
|
Case Closed |
2015-12-10
|
Violation Items
Citation ID |
01001 |
Citaton Type |
Serious |
Standard Cited |
19100119 D02 I D |
Issuance Date |
2015-11-05 |
Abatement Due Date |
2015-12-10 |
Current Penalty |
0.0 |
Initial Penalty |
4675.0 |
Final Order |
2015-12-03 |
Nr Instances |
1 |
Nr Exposed |
5 |
Gravity |
5 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1910.119(d)(2)(i)(D): Information concerning the technology of the process did not include safe upper and lower limits for such items as temperatures, pressures, flows or compositions: 1) On August 24, 2015, and at prior times, the employers process safety information pertaining to the ethane system did not include safe upper pressure limits for the vaporizers. Calculations for the safe upper pressure limit for the vaporizers were based on the pressure rating of a flange which was not an integral part of the vaporizer. |
|
Citation ID |
01002A |
Citaton Type |
Serious |
Standard Cited |
19100119 D03 I B |
Issuance Date |
2015-11-05 |
Abatement Due Date |
2015-12-10 |
Current Penalty |
2500.0 |
Initial Penalty |
4675.0 |
Final Order |
2015-12-03 |
Nr Instances |
3 |
Nr Exposed |
5 |
Gravity |
5 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1910.119(d)(3)(i)(B): Process safety information pertaining to the equipment in the process did not include the piping and instrument diagrams (P&ID's): 1) On August 24, 2015, and at prior times, the P&ID was inaccurate or did not represent existing equipment that was a part of the process in the following instances: a) where the nitrogen pressure regulators for the ethane flow control valves located on the stanchions were not listed on the P&ID. b) where the 250 psi pressure safety valves (PSV 648A and PSV 648B), located at the second state regulator panel, were labeled set at 150 psi. c) where the nitrogen line pressure control valve (PCV 6420) was labeled set at 65 psi, which did not reflect current field settings. |
|
Citation ID |
01002B |
Citaton Type |
Serious |
Standard Cited |
19100119 L01 |
Issuance Date |
2015-11-05 |
Abatement Due Date |
2015-12-03 |
Current Penalty |
0.0 |
Initial Penalty |
0.0 |
Final Order |
2015-12-03 |
Nr Instances |
1 |
Nr Exposed |
5 |
Gravity |
5 |
FTA Current Penalty |
0.0 |
Citation text line |
CFR 1910.119(l)(1): The employer did not establish and implement written procedures to manage changes to process chemicals, technology, equipment, and procedures; and, changes to facilities that affect a covered process: 1) On August 24, 2105, and at prior times, the employer did not ensure that management of change was conducted for a nitrogen regulator that was installed in February 2015 on the nitrogen gas line that is used to operate the ethane flow control valves. |
|
Citation ID |
01003 |
Citaton Type |
Other |
Standard Cited |
19100119 L05 |
Issuance Date |
2015-11-05 |
Abatement Due Date |
2015-12-10 |
Current Penalty |
2500.0 |
Initial Penalty |
4675.0 |
Final Order |
2015-12-03 |
Nr Instances |
1 |
Nr Exposed |
11 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1910.119(l)(5): Where a change covered by this paragraph resulted in a change in the operating procedures or practices required by paragraph (f) of this section, the employer did not ensure that such procedures or practices were updated accordingly: 1) On August 24, 2015, and at prior times, the employer did not ensure that standard operating procedures were updated due to a required management of change in the following instance: a) On February 24, 2014, the employer implemented a management of change related to the installation of a temperature monitor, alarm, and transmitter for the ethane line located after the second stage regulator. This device was installed to provide low temperature protection on the ethane system to protect the piping from any liquid ethane that might pass the vaporizers. The employer did not ensure that standard operating procedures were updated with changes due to this new device. |
|
|
312140924
|
0830600
|
2009-05-22
|
50 WILLIAM WHITE BLVD., PUEBLO, CO, 81001
|
|
Inspection Type |
Planned
|
Scope |
Partial
|
Safety/Health |
Safety
|
Close Conference |
2009-05-22
|
Emphasis |
N: AMPUTATE, S: AMPUTATIONS
|
Case Closed |
2010-01-20
|
Violation Items
Citation ID |
01001 |
Citaton Type |
Other |
Standard Cited |
19100023 A08 I |
Issuance Date |
2009-07-14 |
Abatement Due Date |
2009-08-28 |
Current Penalty |
1125.0 |
Initial Penalty |
1125.0 |
Nr Instances |
1 |
Nr Exposed |
1 |
Gravity |
01 |
|
Citation ID |
01002A |
Citaton Type |
Serious |
Standard Cited |
19100037 B04 |
Issuance Date |
2009-07-14 |
Abatement Due Date |
2009-08-28 |
Current Penalty |
1500.0 |
Initial Penalty |
1500.0 |
Nr Instances |
4 |
Nr Exposed |
4 |
Gravity |
02 |
|
Citation ID |
01002B |
Citaton Type |
Serious |
Standard Cited |
19100037 B06 |
Issuance Date |
2009-07-14 |
Abatement Due Date |
2009-08-28 |
Nr Instances |
4 |
Nr Exposed |
4 |
Gravity |
02 |
|
Citation ID |
01003 |
Citaton Type |
Other |
Standard Cited |
19100212 A01 |
Issuance Date |
2009-07-14 |
Abatement Due Date |
2009-08-28 |
Current Penalty |
1500.0 |
Initial Penalty |
1500.0 |
Nr Instances |
4 |
Nr Exposed |
4 |
Gravity |
02 |
|
Citation ID |
01004 |
Citaton Type |
Other |
Standard Cited |
19100219 C04 I |
Issuance Date |
2009-07-14 |
Abatement Due Date |
2009-08-28 |
Current Penalty |
1500.0 |
Initial Penalty |
1500.0 |
Nr Instances |
5 |
Nr Exposed |
4 |
Gravity |
02 |
|
|
305165326
|
0830600
|
2002-03-11
|
50 WILLIAM WHITE BOULEVARD, PUEBLO, CO, 81001
|
|
Inspection Type |
Complaint
|
Scope |
Partial
|
Safety/Health |
Health
|
Close Conference |
2002-05-08
|
Case Closed |
2002-05-08
|
Related Activity
Type |
Complaint |
Activity Nr |
203483102 |
Health |
Yes |
|
|